633.306 Requirements for installation, inspection, and maintenance of fire suppression equipment.
(1) The requirements for installation of fire extinguishers and preengineered systems are as follows:
(a) Fire equipment dealers shall be licensed under s. 633.304.
(b) Equipment supplied shall be listed by a nationally recognized testing laboratory, such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc. Equipment supplied for new installations or alterations of existing systems must be currently listed as described in this section. The State Fire Marshal shall adopt by rule procedures for determining whether a laboratory is nationally recognized, taking into account the laboratory’s facilities, procedures, use of nationally recognized standards, and any other criteria reasonably calculated to reach an informed determination.
(c) Equipment shall be installed in accordance with the applicable standards of the National Fire Protection Association and the manufacturer’s drawings and specifications, using only components and parts specified by the manufacturer or listed as equal parts by a nationally recognized testing laboratory, such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc.
(d) Each piece of equipment supplied shall be guaranteed for a period of 1 year against defects in material or operation.
(e) The fire equipment dealer shall furnish the consumer with: the manufacturer’s descriptive literature, including the specifications and maintenance requirements as approved by the nationally recognized testing laboratory; the operating instructions for all equipment installed; the mechanical drawings and specifications for proper installation and use of equipment; and a diagram of the final installation, if applicable.
(2) Equipment shall be inspected, serviced, and maintained in accordance with the manufacturer’s maintenance procedures and with the applicable National Fire Protection Association standards.
History.s. 4, ch. 75-240; s. 2, ch. 80-342; s. 3, ch. 84-243; s. 16, ch. 89-233; s. 4, ch. 91-189; s. 3, ch. 98-170; s. 54, ch. 98-419; s. 36, ch. 2013-183; s. 30, ch. 2019-140.